1/2' - BRASS BODY - MANUAL RESET
NORMALLY OPEN
ZDVGRM15NA - FANTINI COSMI
DESCRIPTION
-
Solenoid valves for non-aggressive air and gas (according to EN437) normally open with manual reset.
ELECTRICAL CHARACTERISTICS
-
Nominal voltage 230V AC 50/60Hz
REGULATIONS AND APPROVALS
-
Conforms to standards EN 161-EN60529
INSTALLATION
-
Check the agreement between the flow direction and the arrow embossed on the valve body, check the correct alignment of the connection pipes. The valve can be mounted with a horizontal or vertical coil.
-
The coil can in turn be oriented in any direction within 360°.
- Install in an area protected from rain, splashes or water droplets.
- For electrical connection, remove the connector cover and connect the power cables to the terminals
CHARACTERISTICS
-
Connections: ISO 7/1 threaded gas Rp 1/2 to Rp 2
-
flanged PN16 ISO 7005 from DN65 to DN100
-
Voltage tolerance -15% / +10%
-
Ambient temperature -15°C / +60°C
-
Working pressure 500 mbar Max.
-
Closing time < 1 second
-
Degree of protection IP 54
-
Cable gland PG 9
-
Pressure ports G1/4' on two sides (except models with brass body)
-
Limit switch 3/3" on request 4' to 4'
-
Gas type: air and non-aggressive gases (EN 437)