Gas Safety Solenoid Valve
1/2'' - Brass Body - Manual Reset
Normally Closed
ZDVGRM15NC - Fantini Cosmi
1/2'' - Brass Body - Manual Reset
Normally Closed
ZDVGRM15NC - Fantini Cosmi
Electrical Characteristics
- Rated voltage 230V AC 50/60Hz
Standards and Approvals
- Compliant with EN 161-EN60529 standards
Installation
- Check for consistency between the flow direction and the arrow embossed on the valve body, check the correct alignment of the connection pipes, and maintain a distance from walls to allow free air circulation. The valve can be mounted with the coil horizontal or vertical.
- The coil can be oriented in any direction at 360°.
- Install in an area protected from rain, splashes, or dripping water.
- For electrical connection, remove the connector cover and connect the power cables to the terminals of the rectifier circuit.
Characteristics
- Connections: threaded for gas ISO 7/1 from RP 1/2 to RP 2
- PN16 flange ISO 7005 from DN65 to DN100
- Voltage tolerance -15% / +10%
- Ambient temperature -15°C / +60°C
- Maximum operating pressure 500 mbar
- Closing time < 1 second
- Protection rating IP 65
- Cable gland PG 9
- G1/4'' pressure taps on both sides (except models with brass body)
- Limit switch upon request from 3/4'' to 4''
- Gas type: air and non-aggressive gases (EN 437)
- Filter 600 μm (except models with brass body)
Product Code: ZDVGRM15NC